TDROO Series

Địa chỉ: 21 Đường C18, Phường 12, Quận Tân Bình, Thành phố Hồ Chí Minh, Việt Nam

Hotline: 0903 611 561

Sản phẩm

TDROO Series

Applications

Cooling water

Water supply/distribution/Boosting

Drainage/ Irrigation

General industrial services

Description

Vertical in-line circulation pumps. Standard totally enclosed, fan cooled, insulation class F, IP55 motors. Single phase motors up to 2,2 kW.

Standard versions are suitable for smart pumping of clean water with a temperature range between -15ºC to 110ºC, on request.

F: Cast Iron Impeller

X: SS304 Impeller


  • Liên hệ
  • 377

TDROO Series

Applications
Cooling water
Water supply/distribution/Boosting
Drainage/ Irrigation
General industrial services
Description
Vertical in-line circulation pumps. Standard totally enclosed, fan cooled, insulation class F, IP55 motors. Single phase motors up to 2,2 kW.
Standard versions are suitable for smart pumping of clean water with a temperature range between -15ºC to 110ºC, on request.
F: Cast Iron Impeller
X: SS304 Impeller

Performance range
Capacity: Q up to 750 m3/h
Head: H up to 90 m
Temperature: T up to 110 ºC
Speed: 2900/1450 rpm
3500/1750 rpm
Power: P up to 132 kW
Standard material
Casing: Cast iron
Shaft: Stainless steel
Impeller: Cast iron or stainless steel 304.
Introduction
TDROO Series are single stage in-line centrifugal pumps, equipped with standard motor and mechanical seal. Comparing with other pumps in similar structure, these pumps are less accessible to the impurity in the liquid.
The pump is designed to be pulled out from the top when disassemble.It can be repaired without affecting the pipelines.
The mechanical seal for TF,TX200 and above is cartridge mechanical seal.
Motor needn’t to be disassembled when replace mechanical seal.
TF,TX125—TF,TX150 products have two structures,one is easy maintenance structure, using a catridge mechanical seal. And another is expantion shaft structure.
Curve conditions
Following conditions are suitable for the performance curves shown above.
1. All curves are based on the measured value of motor 3 X380V, 50Hz: under the constant speed of 2900rpm, 1450rpm or 1480rpm; 60Hz: under the constant speed of 3500rpm or 1750rpm; 2. Curve tolerance in conformity with IS09906: 2012,3B.
3. Measurement is done with 20 °C airfree water, without impurities.
4. The operation of pump shall refer to the performance region indicated by the thickened curve to prevent overheating due to too small flow rate or overload of motor due to too large flow rate.
5. If the thickness and density of the pumped liquid is different from water, the motor power should be adjusted.
 

Sản phẩm cùng loại
Zalo
Hotline